1.6. VENTING
In Canada, we recommend that you use a listed pellet vent that meets the ULC S-609-M89/ORD C441-M90
Standard.
For the United States, we recommend that you use a listed pellet vent that meets the UL-641Standard.
This unit can be vented in an existing factory-built or masonry chimney with the addition of a liner, provided
the chimney is more than 4” in diameter. The liner should be listed and should meet the ULC S-635/640
standard in Canada and the UL-1777 standard in the USA. Refer to the instructions provided by the vent or
chimney manufacturer, especially when passing through a wall, ceiling, or roof.
Your venting system should have at least one foot of vertical rise for each foot of horizontal run. The total
vertical rise should never be less than 3 feet (see Appendix A).
This unit uses a pressurized exhaust system. All vent connector joints must be sealed and fastened. If vented
horizontally, joints should be made gastight. Please consult the pellet pipe manufacturer’s instruction to ensure
proper installation and consistent performance to avoid smoke and ash spillage.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
WARNING:
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
WARNING:
DO NOT INSTALL IN SLEEPING ROOM
CAUTION:
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND CEILING/ROOF
MUST BE MAINTAINED
CAUTION:
THE CHIMNEY CONNECTOR SHALL NOT PASS TROUGH AN ATTIC OR ROOF SPACE, CLOSET OR
SIMILAR CONCEALED SPACES, OR FLOORS, OR CEILINGS.
1.6.1. Equivalent Vent Length (EVL)
The longer the run of pipe in your installation, the
greater the restriction in your system.
Always use 4” pipe
Horizontal runs shall not exceed 9 feet.
Never exceed 30 feet of EVL..
To calculate EVL, use the following conversions table:
Qty Type of pipe EVL equivalent(ft)
1 90° elbow or “T” 5
1 45° elbow 3
1 ft Horizontal pipe run 1
1 ft
ertical pipe run 0.5
Here is an example on how to calculate the EVL of
your installation. (See Figure 10):
(3 x 4’ of vertical length = 12’ x 0.5 = 6 EVL) +
(1 x elbow or "T" = 5 EVL) +
(2 x 1’ of horizontal length = 2 EVL)
Total EVL = (6 + 5 +2) = 13.
FIGURE 10
Ventin
g
throu
g
h wall